Fire detection system for commercial ships
Commercial Ships BDS-4000 Fire detection system for the BDS-4000, 12 different loop circuits can be connected to one small central receiving panel. Since 127 transmitters and detectors of ADDRESSABLE TYPE (transmitters and detectors with their own address) can be connected to one loop circuit, a total of 1,524 transmitters, heat, smoke detectors, and flame detectors can be freely connected in a proper mix with all 12 loops. As a Conventional Type (existing method), 32 loops are connected to the small receiver, and one loop can connect 200 transmitters, detectors and flame detectors, so a total of 6,400 detectors, transmitters and flame detectors can be connected in a proper mix.
All transmitters, smoke detectors, heat detectors and flame detectors are connected to the interface unit by a loop circuit, and data transmitted from the detector and transmitter to the interface unit are transferred to the 7.0” touch screen central receiver.
BDS-4000 can be interfaced to the existing BDS-2000 (various gas detection receiver) by RS-485 communication method, so this BDS-4000 model can be used as a FIRE & GAS DETECTION SYSTEM.
All data of the BDS-4000 receiver can be outputted to a computer through TCP-IP LAN PORT, and DATA BACK UP and SOFTWARE UPGRADE are possible using USB PORT.
The advantage of the BDS-4000 is that various types of detectors can be freely connected to the central receiver via the interface unit, so an unlimited number of detectors and transmitters can be connected by adding a small 7” central receiver.
In addition, this product has obtained a certificate for use in various artificial intelligence buildings, petrochemical plants, offshore plants, ships and gas plants.
Primary power | AC 115 / AC 230 VAC |
Secondary power | 230 VAC or DC 24V |
Emergency battery | 24 VAC 12 AH (24 hours emergency operation possible) |
Power consumption | Max. 150W |
Ambient operating temperature | -5? ~ 55? |
Maximum electrical cable length | 1.2 km |
Center receiving panel size | 272 (H) x 138 (L) x 72 (W) mm |
Center receiving panel weight | About 5kg |
2 USB memory card | System upgrade and setting change |
Read More :
Rheonik Fuel Consumption For Marine Application, Rheonik Coriolis mass flow meters have been used for…
Coriolis Mass Flow Meters For Marine Fuel Consumption Application, Rheonik Coriolis mass flow meters have…
In commercial shipping, now more than ever, fuel consumption measurements are an important part of…
In commercial shipping, now more than ever, fuel consumption measurements are an important part of…
Mengukur konsumsi bahan bakar di sebuah mesin atau engine, disini kita melihat penjelasan bagaimana bahan…
Mengukur Konsumsi Bahan Bakar di Kapal Dengan Fluidwell Tipe F127 Mengukur konsumsi bahan bakar di…
This website uses cookies.